4.2.2 Displayed state of running parameters
After the inverter receives valid running commands, the inverter will enter into the running state and the
keypad will display the running parameters. RUN/TUNE LED on the keypad is on, while the FWD/REV is
determined by the current running direction which is shown as figure 4-2.
In the running state, there are 24 parameters can be selected to be displayed or not. They are: running
frequency, set frequency, bus voltage, output voltage, output torque, PID given, PID feedback, input
terminals state, output terminals state, torque set value, length value, PLC and the current stage of
multi-step speeds, pulse counting value, AI1, AI2, AI3, HDI, percentage of motor overload, percentage of
inverter overload, ramp given value, linear speed, AC input current. P07.05 and P07.06 can select the
parameter to be displayed or not by bit and 》/SHIFT can shift the parameters from left to right, QUICK/JOG
(P07.02=2) can shift the parameters from right to left.
4.2.3 Displayed state of fault
If the inverter detects the fault signal, it will enter into the fault pre-alarm displaying state. The keypad will
display the fault code by flicking. The TRIP LED on the keypad is on, and the fault reset can be operated by
the STOP/RST on the keypad, control terminals or communication commands.
4.2.4 Displayed state of function codes editing
In the state of stopping, running or fault, press PRG/ESC
to enter into the editing state (if there is a
password, see P07.00 ).The editing state is displayed on two classes of menu, and the order is: function
code group/function code number→function code parameter, press DATA/ENT into the displayed state of
function parameter. On this state, press DATA/ENT to save the parameters or press
PRG/ESC to escape.
Figure 4-2 Displayed state

4.3 Keypad operation

Operate the inverter via operation panel. See the detailed structure description of function codes in the brief
diagram of function codes.
4.3.1 How to modify the function codes of the inverter
The inverter has three levels menu, which are:
1. Group number of function code (first-level menu)
2. Tab of function code (second-level menu)
3. Set value of function code (third-level menu)
Remarks: Press both the PRG/ESC and the DATA/ENT can return to the second-level menu from the
third-level menu. The difference is: pressing DATA/ENT will save the set parameters into the control panel,
and then return to the second-level menu with shifting to the next function code automatically; while pressing
PRG/ESC will directly return to the second-level menu without saving the parameters, and keep staying at
the current function code.
Keypad Operation Procedure
25 - 140