Function
Name
code
changing ratio
Action
selection for
P08.47
frequency
settings on
power off
High bit of
P08.48
initial power
consumption
Low bit of initial
P08.49
power
consumption
Magnetic flux
P08.50
braking
coefficient
Input power
P08.51
factor of the
inverter
Function Parameters
Detailed instruction of parameters
0x000~0x111
LED ones: Action for digital adjustable frequency on power
off
0: Save on power off
1: Clear on power off
LED tens: Action for MODBUS frequency setting on power
off
0: Save on power off
1: Clear on power off
LED hundreds: Action for other-mode frequency setting on
power off
0: Save on power off
1: Clear on power off
This parameter is used to set the original value of the power
consumption.
The original value of the power consumption =P08.48*1000+
P08.49
Setting range of P08.48: 0~59999 kWh (x1000)
Setting range of P08.49:0.0~999.9 kWh
This function code is used to enable magnetic flux.
0: Invalid.
100~150: the bigger the coefficient, the stronger the braking
strength.
The inverter can slow down the motor by increasing the magnetic
flux. The energy generated by the motor during braking can be
transformed into heat energy by increasing the magnetic flux.
The inverter monitors the state of the motor continuously
even during the magnetic flux period. So the magnetic flux
can be used in the motor stop, as well as to change the
rotation speed of the motor. Its other advantages are:
Brake immediately after the stop command. It does not need
to wait the magnetic flux weaken.
The cooling is better. The current of the stator other than the
rotor increases during magnetic flux braking, while the
cooling of the stator is more effective than the rotor.
This function code is used to adjust the displayed current of
the AC input side.
Setting range: 0.00~1.00
P09 Group
PID control
Default
Modify
value
0x000
0 kWh
0.0 kWh
0
0.56
71 - 140