 CV30 inverters should be installed in a clean and ventilated environment according to enclosure
classification.
 Cooling air must be clean, free from corrosive materials and electrically conductive dust.
3.1.2 Installation direction
The inverter may be installed on the wall or in a cabinet.
The inverter needs to be installed in the vertical position. Check the installation site according to the
requirements below. Refer to chapter Dimension Drawings in the appendix for frame details.
3.1.3 Installation manner
(1) Wall and rail mounting for the inverters 1PH 230V-3PH 400V≤2.2kW and 3PH 220V≤0.75kW:
Note: the minimum space of A and B is 100mm if H is 36.6mm and W is 35.0mm.
(2) Wall and flange mounting for the inverters 3PH 400V≥4kW and 3PH 220V≥1.5kW:
Installation Guidelines
Below 1000m
If the sea level is above 1000m, please derate 1% for every additional 100m.
2
≤ 5.8m/s
(0.6g)
The inverter should be installed on an upright position to ensure sufficient
cooling effect.
a)
Wall mounting
Figure 3-1 Installation
Conditions
b) Rail mounting