Function
Name
code
The parameter
P07.07
selection of the
stop state
Frequency
P07.08
display
coefficient
Rotation speed
P07.09
display
coefficient
Linear speed
P07.10
display
coefficient
Rectifier bridge
P07.11
module
temperature
Inverter
P07.12
module
temperature
Software
P07.13
version
Local
P07.14
accumulative
60 - 140
Detailed instruction of parameters
BIT6: ramp frequency given value (Hz on)
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9~15: reserved
0x0000~0xFFFF
BIT0: set frequency (Hz on, frequency flickering slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID reference (% flickering)
BIT5: PID feedback value (% flickering)
BIT6: torque reference (% flickering)
BIT7: analog AI1 value (V on)
BIT8: analog AI2 value (V on)
BIT9: analog AI3 value (V on)
BIT10: high speed pulse HDI frequency
BIT11: PLC and the current stage of multi-step speed
BIT12: pulse counters
BIT13~BIT15: reserved
Example- Default Value: 0000 0000 1111 1111
0.01~10.00
Displayed frequency=running frequency* P07.08
0.1~999.9%
Mechanical rotation speed =120*displayed running
frequency×P07.09/motor pole pairs
0.1~999.9%
Linear speed= Mechanical rotation speed×P07.10
-20.0~120.0°C
-20.0~120.0°C
1.00~655.35
0~65535h
Default
Modify
value
0x00FF
1.00
100.0%
1.0%
Fault Tracking