Salicru CV30 User Manual page 29

Inverter controlvit
Table of Contents

Advertisement

Function
Name
code
Speed control
P00.00
mode
Run command
P00.01
channel
Max. output
P00.03
frequency
Function Parameters
Detailed instruction of parameters
P00 Group Basic function group
0: SVC 0
No need to install encoders. Suitable in applications which
need low frequency, big torque for high accuracy of rotating
speed and torque control. Relative to mode 1, it is more
suitable for the applications which need small power.
1: SVC 1
Is suitable in high performance cases with the advantage of
high accuracy of rotating speed and torque. It does not need
to install pulse encoder.
2: SVPWM control
Is suitable in applications which do not need high control
accuracy, such as the load of fan and pump. One inverter
can drive multiple motors.
Select the run command channel of the inverter.
The control command of the inverter includes: start, stop,
forward/reverse rotating, jogging and fault reset.
0: Keypad running command channel ("LOCAL/REMOT"
light off)
Carry out the command control by RUN, STOP/RST on the
keypad.
Set the multi-function key QUICK/JOG to FWD/REV shifting
function (P07.02=3) to change the running direction; press
RUN and STOP/RST simultaneously in running state to
make the inverter coast to stop.
1: Terminal running command channel
("LOCAL/REMOT" flickering)
Carry out the running command control by the forward
rotation, reverse rotation and forward jogging and reverse
jogging of the multi-function terminals
2: Communication running command channel
("LOCAL/REMOT" on);
The running command is controlled by the upper monitor via
communication
This parameter is used to set the maximum output frequency
of the inverter. Users need to pay attention to this parameter
because it is the foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
Default
Modify
value
1
0
50.00Hz
29 - 140