Function
Name
code
sequence of
running
command
STOP/RST
P07.04
stop function
Displayed
P07.05
parameters 1
of running state
Displayed
P07.06
parameters 2
of running state
Function Parameters
Detailed instruction of parameters
0: Keypad control→terminals control →communication
control
1: Keypad control←→terminals control
2: Keypad control←→communication control
3: Terminals control←→communication control
Select the stop function by STOP/RST. STOP/RST is
effective in any state for the keypad reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication control
3: Valid for all control modes
0x0000~0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency(Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage (V on)
BIT4: output current (A on)
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID reference (% flickering)
BIT9: PID feedback value (% on)
BIT10: input terminals state
BIT11: output terminals state
BIT12: torque set value (% on)
BIT13: pulse counter value
BIT14: reserved
BIT15: PLC and the current stage of multi-step speed
Example- Default value: 0000 0011 1111 1111
0x0000~0xFFFF
BIT0: analog AI1 value (V on)
BIT1: analog AI2 value (V on)
BIT2: analog AI3 value (V on)
BIT3: high speed pulse HDI frequency
BIT4: motor overload percentage (% on)
BIT5: the inverter overload percentage (% on)
Default
Modify
value
0
0x03FF
0x0000
59 - 140