Salicru CV30 User Manual page 47

Inverter controlvit
Table of Contents

Advertisement

Function
Name
code
Low frequency
P04.10
vibration
control factor
High frequency
P04.11
vibration
control factor
Vibration
P04.12
control
threshold
Energy-saving
P04.26
operation
selection
Voltage Setting
P04.27
channel
Keypad setting
P04.28
voltage
Voltage
P04.29
increasing time
Voltage
P04.30
decreasing
time
Output
P04.31
maximum
voltage
Function Parameters
Detailed instruction of parameters
Setting range: 0.0~200.0%
In the SVPWM control mode, current fluctuation may occur to the
motor on some frequency, especially the motor with big power.
The motor can not run stably or overcurrent may occur. These
phenomena can be canceled by adjusting this parameter.
The setting range of P04.10: 0~100
The setting range of P04.11: 0~100
The setting range of P04.12: 0.00Hz~P00.03(the Max.
frequency)
0: No operation
1: Automatic energy-saving operation
Motor on the light load conditions, automatically adjusts the
output voltage to save energy
Select the output setting channel at V/f curve separation.
0: Keypad setting voltage. The output voltage is determined
by P04.28.
1: AI1 setting voltage
2: AI2 setting voltage
3: AI3 setting voltage
4: HDI setting voltage
5: Multi-step speed setting voltage
6: PID setting voltage
7: MODBUS communication setting voltage
8~10: Reserved
Note: 100% corresponds to the rated voltage of the motor.
The function code is the voltage digital set value when the
voltage setting channel is selected as "keypad selection"
The setting range: 0.0%~100.0%
Voltage increasing time is the time when the inverter
accelerates from the output minimum voltage to the output
maximum voltage.
Voltage decreasing time is the time when the inverter
decelerates from the output maximum voltage to the output
minimum voltage.
The setting range: 0.0~3600.0s
Set the upper and low limit of the output voltage.
The setting range of P04.31: P04.32~100.0%
(the rated voltage of the motor)
Default
Modify
value
10
10
30.00
Hz
0
0.0%
100.0%
5.0s
5.0s
100.0%
47 - 140