Function
Name
code
during fault
Speed
P11.14
deviation
detection
Speed
P11.15
deviation
detection time
Automatic
frequency
P11.16
decreasing at
voltage drop
P13 Group Control parameters of Short circuit braking
Braking
P13.13
current of
short circuit
Braking
retention time
P13.14
of starting
short circuit
Braking
retention time
P13.15
of stopping
short circuit
82 - 140
Detailed instruction of parameters
0x00~0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0.0~50.0%
Set the speed deviation detection time.
This parameter is used to set the speed deviation detection
time.
Setting range of P11.15: 0.0~10.0s
0: Invalid
1: Valid; ensure rated output torque when voltage drop
After the inverter starts, when P01.00=0, set P13.14 to
non-zero value and begin short circuit braking.
After the inverter stops, when the operation frequency is less
than P01.09, set P13.15 to non-zero value and begin
stopping short-circuit braking and then DC braking.
Setting range of P13.13: 0.0~150.0% (inverters)
Setting range of P13.14: 0.00~50.00s
Default
Modify
value
10.0%
0.5s
0x00
0.0%
0.00s
0.00s