Function
Specification
Speed fluctuation
± 0.3% (SVC)
Torque response
<20ms (SVC)
Torque control accuracy
10%
Starting torque
0. 5Hz/150% (SVC)
150% of rated current: 1 minute
Overload capability
180% of rated current: 10 seconds
200% of rated current: 1 second
Digital setting, analog setting, pulse frequency setting,
multi-step speed running setting, simple PLC setting, PID
Frequency setting method
setting, MODBUS communication setting
Shift between the set combination and set channel.
Running
Auto-adjustment of the
Keep a stable voltage automatically when the grid voltage
control
voltage
transients
feature
Provide comprehensive fault protection functions:
Fault protection
overcurrent, overvoltage, undervoltage, overheating,
phase loss and overload, etc.
Start after speed tracking
Smoothing starting for running motor
Analog input
1 (AI2) 0~10V/0~20mA and 1 (AI3) -10~10V
Analog output
2 (AO1, AO2) 0~10V/0~20mA
4 common inputs, the Max. frequency: 1kHz;
Digital input
1 high speed input, the Max. frequency: 50kHz
Peripheral
Digital output
1 programmable digital output (Y1)
interface
2 programmable relay outputs
RO1A NO, RO1B NC, RO1C common terminal
Relay output
RO2A NO, RO2B NC, RO2C common terminal
Contact capacity: 3A/AC250V
Temperature of the
-10~50°C, derate 1% for every additional 1℃ when
running environment
above 40℃
Wall and DIN rail installation for the following inverters:
single-phase 230V / three-phase 400V ≤ 2.2KW and
Installation mode
three-phase 220V≤0.75KW
Wall and flange installation for the following inverters:
three-phase 380V≥4KW and three-phase 220V≥1.5KW)
Others
Braking unit
Embedded
IP20
Note: The inverter with plastic casing should be installed
Protection degree
in metal distribution cabinet, which conforms to IP20 and
of which the top conforms to IP3X.
Cooling
Air-cooling
Product overview
9 - 140