Salicru CV30 User Manual page 48

Inverter controlvit
Table of Contents

Advertisement

Function
Name
code
Output
P04.32
minimum
voltage
Weakening
coefficient in
P04.33
constant
power zone
HDI input
P05.00
selection
S1 terminals
P05.01
function
selection
S2 terminals
P05.02
function
selection
S3 terminals
P05.03
function
selection
S4 terminals
P05.04
function
selection
48 - 140
Detailed instruction of parameters
The setting range of P04.32: 0.0%~ P04.31
Adjust the output voltage of the inverter in SVPWM mode
when weakening.
Note: Invalid in the constant torque mode.
The setting range of P04.33: 1.00~1.30
P05 Group Input terminals
0: HDI is high pulse input. See P05.49~P05.54
1: HDI is switch input (same as S1~S4 terminals)
Note: S1~S4 and HDI are terminals on the control board,
and P05.12 can be used to set the function of S5~S8, that
are virtual terminals
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
Default
Modify
value
0.0%
1.00
0
1
4
7
0
Fault Tracking