Salicru CV30 User Manual page 36

Inverter controlvit
Table of Contents

Advertisement

Function
Name
code
ACC time of
P01.06
the starting
step of S curve
DEC time of
P01.07
the ending step
of S curve
Stop mode
P01.08
selection
Starting
P01.09
frequency of
DC braking
Waiting time
P01.10
before DC
braking
DC braking
P01.11
current
DC braking
P01.12
time
36 - 140
Detailed instruction of parameters
0.0~50.0s
0: Decelerate to stop. After the stop command becomes
valid, the inverter decelerates to reduce the output frequency
during the set time. When the frequency decreases to 0Hz,
the inverter stops.
1: Coast to stop. After the stop command becomes valid,
the inverter ceases the output immediately. And the load
coasts to stop at the mechanical inertia.
Starting frequency of DC braking: start the DC braking
when running frequency reaches starting frequency
determined by P1.09.
Waiting time before DC braking: Inverters blocks the
output before starting the DC braking. After this waiting time,
the DC braking will be started so as to prevent over-current
fault caused by DC braking at high speed.
DC braking current: the value of P01.11 is the percentage
of rated current of inverter. The bigger the DC braking
current is, the greater the braking torque is.
DC braking time: the retention time of DC braking. If the
time is 0, the DC braking is invalid. The inverter will stop at
the set deceleration time.
Default
Modify
value
0.1s
0.1s
0
0.00Hz
0.00s
0.0%
0.00s
Fault Tracking