2 Product Overview

2.1 Quick start-up

2.1.1 Unpacking inspection

Check as follows after receiving products:
1. Check that there are no damage and humidification to the package. If not, please contact with local
dealers or SALICRU offices.
2. Check the information on the type designation label on the outside of the package to verify that the drive
is of the correct type. If not, please contact with local dealers or SALICRU offices.
3. Check that there are no signs of water in the package and no signs of damage or breach to the inverter.
If not, please contact with local dealers or SALICRU offices.
4. Check the information on the type designation label on the outside of the package to verify that the name
plate is of the correct type. If not, please contact with local dealers or SALICRU offices.
5. Check to ensure the accessories (including user's manual and control keypad) inside the device is
complete. If not, please contact with local dealers or SALICRU offices.

2.1.2 Application confirmation

Check the machine before beginning to use the inverter:
1. Check the load type to verify that there is no overload of the inverter during work and check that whether
the drive needs to modify the power degree.
2. Check that the actual current of the motor is less than the rated current of the inverter.
3. Check that the control accuracy of the load is the same of the inverter.
4. Check that the incoming supply voltage is correspondent to the rated voltage of the inverter.

2.1.3 Environment

Check as follows before the actual installation and usage:
1. Check that the ambient temperature of the inverter is below 40°C. If exceeds, derate 1% for every
additional 1°C. Additionally, the inverter can not be used if the ambient temperature is above 50°C.
Note: for the cabinet inverter, the ambient temperature means the air temperature inside the cabinet.
2. Check that the ambient temperature of the inverter in actual usage is above -10°C. If not, add heating
facilities.
Note: for the cabinet inverter, the ambient temperature means the air temperature inside the cabinet.
3. Check that the altitude of the actual usage site is below 1000m. If exceeds, derate 1% for every
additional 100m.
4. Check that the humidity of the actual usage site is below 90% and condensation is not allowed. If not,
add additional protection to the inverters.
5. Check that the actual usage site is away from direct sunlight and foreign objects can not enter the
inverter. If not, add additional protective measures.
6. Check that there is no conductive dust or flammable gas in the actual usage site. If not, add additional
protection to inverters.