Function
Name
code
Local
P14.00
communication
address
P14.01
Baud rate
Digital bit
P14.02
checkout
setting
Function Parameters
Detailed instruction of parameters
P14 Group Serial communication
The setting range: 1~247
When the master is writing the frame, the communication
address of the slave is set to 0; the broadcast address is the
communication address. All slaves on the MODBUS fieldbus
can receive the frame, but the slave doesn't answer.
The communication address of the drive is unique in the
communication net. This is the fundamental for the point to
point communication between the upper monitor and the drive.
Note: The address of the slave cannot set to 0.
Set the digital transmission speed between the upper
monitor and the inverter.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
Note: The baud rate between the upper monitor and the
inverter must be the same. Otherwise, the communication is
not applied. The bigger the baud rate, the quicker the
communication speed.
The data format between the upper monitor and the inverter
must be the same. Otherwise, the communication is not
applied.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3: No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check(O,8,2) for RTU
6: No check(N,7,1)for ASCII
7: Even check(E,7,1)for ASCII
8: Odd check(O,7,1)for ASCII
9: No check(N,7,2)for ASCII
10: Even check(E,7,2)for ASCII
11: Odd check(O,7,2)for ASCII
12: No check(N,8,1)for ASCII
Default
Modify
value
1
4
1