Function
Name
code
Terminal
running
P01.18
protection
selection when
powering on
The running
frequency is
lower than the
lower limit one
P01.19
(valid if the
lower limit
frequency is
above 0)
Hibernation
P01.20
restore delay
time
38 - 140
Detailed instruction of parameters
Setting range: 0.00~100.00s (only valid when P01.16=1)
When the running command channel is the terminal control,
the system will detect the state of the running terminal during
powering on.
0: The terminal running command is invalid when
powering on. Even the running command is detected to be
valid during powering on, the inverter won't run and the
system keeps in the protection state until the running
command is canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is detected to be valid
during powering on, the system will start the inverter
automatically after the initialization.
Note: This function should be selected with caution, or
serious result may follow.
This function code determines the running state of the inverter
when the set frequency is lower than the lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set frequency is lower
than the lower-limit one. If the set frequency is above the lower
limit one again and it lasts for the time set by P01.20, the
inverter will come back to the running state automatically.
This function code determines the hibernation delay time.
When the running frequency of the inverter is lower than the
lower limit one, the inverter will stop to stand by.
When the set frequency is above the lower limit one again
and it lasts for the time set by P01.20, the inverter will run
automatically.
Default
Modify
value
0
0
0.0s