Function
Name
code
Output upper
P09.09
limit of PID
Output lower
P09.10
limit of PID
Feedback
P09.11
offline
detection value
Feedback
P09.12
offline
detection time
PID adjustment
P09.13
selection
74 - 140
Detailed instruction of parameters
Setting range: 0.0~100.0%
These parameters are used to set the upper and lower limit
of the PID adjustor output.
100.0 % corresponds to Max. Frequency or the Max. Voltage
of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
Set the PID feedback offline detection value when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the set
value in P09.12, the inverter will report "PID feedback offline
fault" and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0x0000~0x1111
LED ones:
0: Keep on integral adjustment when the frequency achieves
the upper and low limit; the integration shows the change
Default
Modify
value
100.0%
0.0%
0.0%
1.0s
0x0001