Function
Name
code
Upper limit of
P00.04
the running
frequency
Lower limit of
P00.05
the running
frequency
A frequency
P00.06
command
selection
B frequency
P00.07
command
selection
30 - 140
Detailed instruction of parameters
The upper limit of the running frequency is the upper limit of
the output frequency of the inverter which is lower than or
equal to the maximum frequency.
Setting range:P00.05~P00.03 (Max. output frequency)
The lower limit of the running frequency is that of the output
frequency of the inverter.
The inverter runs at the lower limit frequency if the set
frequency is lower than the lower limit.
Note: Max. output frequency ≥ Upper limit frequency ≥
Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the running
frequency)
Note: A frequency and B frequency can not set as the same
frequency given method. The frequency source can be set
by P00.09.
0: Keypad data setting
Modify the value of function code P00.10 to set the
frequency.
1: Analog AI1 setting (corresponding to the keypad
potentiometer)
2: Analog AI2 setting (corresponding terminal AI2)
3: Analog AI3 setting (corresponding terminal AI3)
Set the frequency by analog input terminals. CV30 inverters
provide 3 channels analog input terminals as the standard
configuration, of which AI1 is adjusted through analog
potentiometer, while AI2 is the voltage/current option
(0~10V/0~20mA) which can be shifted by dip switch; while
AI3 is voltage input (-10V~+10V).
Note: when analog AI2 select 0~20mA input, the
corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to the
maximum frequency (function code P00.03) in forward
direction and -100.0% corresponds to the maximum
frequency in reverse direction (function code P00.03)
4: High-speed pulse HDI setting
The frequency is set by high-speed pulse terminals. CV30
inverters provide 1 high speed pulse input as the standard
configuration. The pulse frequency range is 0.00~50.00kHz.
100.0% of the high speed pulse input setting corresponds to
the maximum frequency in forward direction (function code
P00.03) and -100.0% corresponds to the maximum