Function
Name
code
P08.01
DEC time 2
P08.02
ACC time 3
P08.03
DEC time 3
P08.04
ACC time 4
P08.05
DEC time 4
Jogging
P08.06
running
frequency
Jogging
P08.07
running ACC
time
Jogging running
P08.08
DEC time
Jumping
P08.09
frequency 1
Jumping
P08.10
frequency
range 1
Jumping
P08.11
frequency 2
Jumping
P08.12
frequency
range 2
Jumping
P08.13
frequency 3
Jumping
P08.14
frequency
range 3
Traverse range This function applies to the industries where traverse and
P08.15
P08.16
Sudden
Function Parameters
Detailed instruction of parameters
CV30 inverters define four groups of ACC/DEC time which
can be selected by P5 group. The first group of ACC/DEC
time is the factory default one.
Setting range: 0.0~3600.0s
This parameter is used to define the reference frequency
during jogging.
Setting range: 0.00Hz ~P00.03 (the Max. frequency)
The jogging ACC time means the time needed if the inverter
runs from 0Hz to the Max. Frequency.
The jogging DEC time means the time needed if the inverter
goes from the Max. Frequency (P00.03) to 0Hz.
Setting range: 0.0~3600.0s
When the set frequency is in the range of jumping frequency,
the inverter will run at the edge of the jumping frequency.
The inverter can avoid the mechanical resonance point by
setting the jumping frequency. The inverter can set three
jumping frequencies. But this function will be invalid if all
jumping points are 0.
Setting range: 0.00~P00.03 (the Max. frequency)
convolution function are required such as textile and
chemical fiber.
Default
Modify
value
on model
Depends
on model
Depends
on model
Depends
on model
Depends
on model
Depends
on model
5.00Hz
Depends
on model
Depends
on model
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.00Hz
0.0%
0.0%