Salicru CV30 User Manual page 37

Inverter controlvit
Table of Contents

Advertisement

Function
Name
code
Dead time of
P01.13
FWD/REV
rotation
Switching
between
P01.14
FWD/REV
rotation
Stopping
P01.15
speed
Detection of
P01.16
stopping speed
Detection time
P01.17
of the feedback
speed
Function Parameters
Detailed instruction of parameters
Setting range of P01.09: 0.00Hz~P00.03 ( Max. frequency)
Setting range of P01.10: 0.00~50.00s
Setting range of P01.11: 0.0~100.0%
Setting range of P01.12: 0.00~50.00s
During the procedure of switching FWD/REV rotation, set the
threshold by P01.14, which is as the table below:
Setting range: 0.0~3600.0s
Set the threshold point of the inverter:
0: Switch after zero frequency
1: Switch after the starting frequency
2: Switch after the speed reach P01.15 and delay for P01.24
0.00~100.00Hz
0: Detect at the setting speed
1: Detect at the feedback speed (only valid for vector
control)
When P01.16=1, the actual output frequency of the inverter
is less than or equal to P01.15 and is detected during the
time set by P01.17, the inverter will stop; otherwise, the
inverter stops in the time set by P01.24.
Default
Modify
value
0.0s
0
0.50Hz
1
0.50s
37 - 140