Salicru CV30 User Manual page 96

Inverter controlvit
Table of Contents

Advertisement

Fault code
OL2
Inverter overload
OL3
Electrical overload
SPI
Input phase loss
SPO
Output phase loss
OH1
Rectifier overheat
OH2
IGBT overheat
EF
External fault
CE
Communication error
96 - 140
Fault type
1. The acceleration is too fast
2. Reset the rotating motor
3. The voltage of the power
supply is too low.
4. The load is too heavy.
5. Close loop vector control,
reverse direction of the code
panel and long low-speed
operation
The inverter will report overload
pre-alarm according to the set
value.
Phase loss or fluctuation of input
R,S,T
U,V,W phase loss (or serious
asymmetrical three phase of the
load)
1. Air duct jam or fan damage
2. Ambient temperature is too
high.
3. The time of overload running
is too long.
S1...S4 external fault input
terminals action
1. The baud rate setting is
incorrect.
2. Fault occurs to the
communication wiring.
3. The communication address
is wrong.
4. There is strong interference to
the communication.
Possible cause
What to do
1. Increase the ACC time
2. Avoid the restarting after
stopping.
3. Check the power of the supply
line
4. Select an inverter with bigger
power.
5. Check the setting of relative
function codes.
Check the load and the overload
pre-alarm point.
1. Check input power
2. Check installation distribution
1. Check the output distribution
2. Check the motor and cable
1. Refer to the overcurrent
solution
2. Redistribute
dredge the wind channel or
change the fan
3. Low the ambient temperature
4. Check and reconnect
5. Change the power
6. Change the power unit
7. Change the main control
panel
Check the external device input
1. Set proper baud rate
2. Check the communication
connection distribution
3. Set proper communication
address.
4. Change or replace the
connection distribution or
improve the anti-interference
capability.
Fault Tracking