When a program is divided into multiple program blocks, the END instruction indicates the end of a program
block.
The END instruction within the program registered at the end of the program setting performs END
processing.
Operation error
Error code
Description
(SD0)
3340H
After execution of the FOR instruction, the END instruction is executed before the NEXT instruction.
3381H
After execution of the CALL(P), FCALL(P), ECALL(P), or EFCALL(P) instruction, the END instruction is executed before the RET
instruction.
33A1H
Within the interrupt program specified by the interrupt pointer (I), the END instruction is executed before the IRET instruction.