Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 277

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Processing details
• These instructions multiply the BCD 4-digit data in the device specified by (s1) by the BCD 4-digit data in the device
specified by (s2), and store the operation result in the device specified by (d). ((d)+1: Upper 4 digits, (d): Lower 4 digits)
(s1)
5
6
7
8
×
0
Operation error
Error code
Description
(SD0)
3405H
The BCD data in the device specified by (s1) is out of the range, 0 to 9999.
The BCD data in the device specified by (s2) is out of the range, 0 to 9999.
(s2)
(d)+1
8
7
6
0
4
9
Filled with 0.
(d)
7
3
9
2
8
6.2 Arithmetic Operation Instructions
6 BASIC INSTRUCTIONS
275
6