B+(P) [when three operands are set]
RnPCPU
RnCPU RnENCPU
(Process)
These instructions add the two sets of BCD 4-digit data specified.
Ladder
(s1)
FBD/LD
EN
ENO
s1
d
s2
( is to be replaced by either of the following: BPLUS, BPLUSP.)
■Execution condition
Instruction
B+
B+P
Setting data
■Description, range, data type
Operand
Description
(s1)
First addend data or the device where the first addend data
is stored
(s2)
Second addend data or the device where the second
addend data is stored
(d)
Device for storing the operation result
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s1)
(s2)
(d)
6 BASIC INSTRUCTIONS
260
6.2 Arithmetic Operation Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(s2)
(d)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
ST
ENO:=BPLUS(EN,s1,s2,d);
ENO:=BPLUSP(EN,s1,s2,d);
Range
0 to 9999
0 to 9999
Double word
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
BCD 4-digit
ANY16
BCD 4-digit
ANY16
BCD 4-digit
ANY16
Bit
BOOL
Bit
BOOL
Indirect
Constant
specification
LZ
K, H E
Others
$