Using a Programming Console
Panel Installation
8-1-2
Compatible Programming Consoles
ed while a time-consuming operation (such as a program check) is being
performed.
The C200H-PRO27-E Programming Console can be installed in a control
panel as shown in the following diagram. (The C200H-ATT01 Mounting
Bracket is sold separately.)
Mounting Bracket
Panel thickness: 1.0 to 3.2 mm
Allow at least 80 mm for the cable connector above the Programming Con-
sole.
37
There are 3 Programming Consoles that can be used with the CPM2C-S: The
CQM1H-PRO01-E, CQM1-PRO01-E and the C200H-PRO27-E. The key func-
tions for these Programming Consoles are identical.
Press and hold the Shift Key to input a letter shown in the upper-left corner of
the key or the upper function of a key that has two functions. For example, the
CQM1-PRO01-E's AR/HR Key can specify either the AR or HR Area; press
and release the Shift Key and then press the AR/HR Key to specify the AR
Area.
Mounting hole dimensions
(DIN43700 standards)
Two screws
15
At least 80 mm is required.
Either connector may
be used.
About 70 mm is required.
Section 8-1
+1.1
186
−0
+0.8
92
−0
161