PC Setup
4-6-2

PC Setup Settings

Word(s)
Bit(s)
PC Startup Processing (DM 6600 to DM 6614)
The following settings are read by the CPU when the PC is turned ON.
DM 6600
00 to 07
Startup mode (effective when bits 08 to 15 are set to 02).
00 (Hex): PROGRAM; 01 (Hex): MONITOR; 02 (Hex): RUN
08 to 15
Startup mode designation
00 (Hex):
01 (Hex):
02 (Hex):
DM 6601
00 to 07
Not used.
08 to 11
IOM Hold Bit (SR 25212) Status at Startup
0 (Hex): Reset to 0; 1 (Hex): Maintain previous status
12 to 15
Forced Status Hold Bit (SR 25211) Status at Startup
0 (Hex): Reset to 0; 1 (Hex): Maintain previous status
DM 6602
00 to 03
Program memory write-protection
0 (Hex): Program memory unprotected
1 (Hex): Program memory write-protected (except DM 6602 itself)
04 to 07
Programming Console display language
0 (Hex): English; 1 (Hex): Japanese
08 to 11
Expansion instruction function code assignments
0 (Hex): Default settings
1 (Hex): User assignments
12 to 15
Not used.
DM 6603
00 to 03
Maximum number of CompoBus/S nodes
0 (Hex): 256-point mode (32 nodes)
1 (Hex): 128-point mode (16 nodes)
04 to 07
CompoBus/S communications mode
0 (Hex): High-speed mode
1 (Hex): Long-distance mode
08 to 15
Not used.
DM 6604
00 to 07
00 (Hex): A memory error will not be generated if data could not be retained by the battery.
01 (Hex): A memory error will be generated if data could not be retained by the battery.
08 to 15
Not used.
DM 6605
00 to 03
DeviceNet Read/Write area settings
0 (Hex): Read area (IN) IR 020 to IR 027; Write area (OUT) IR 030 to IR 037
1 (Hex): Use settings in DM 6606 to DM 6609.
04 to 07
Transmission of CPM2C-S status to the DeviceNet Master
0 (Hex): Attach status information ahead of data.
1 (Hex): Do not attach status information ahead of data.
08 to 15
Not used.
DM 6606
00 to 07
DeviceNet I/O Link Write
(OUT) area settings
(Master → CPM2C-S)
08 to 15
DM 6607
00 to 15
100
According to the setting on DIP switch pin 4 and peripheral port connection
(See table at the bottom of this page.)
Continue operating mode last used before power was turned OFF.
Use setting in bits 00 to 07.
Data area
01 (Hex): I/O area 1 (IR 000 to IR 049)
02 (Hex): I/O area 2 (IR 200 to IR 227)
03 (Hex): DM area (DM 0000 to DM 2047)
04 (Hex): LR area (LR 00 to LR 15)
05 (Hex): HR area (HR 00 to HR 19)
07 (Hex): Timer/counter area (TC 000 to TC 255)
Number of bytes
01 to 40 (Hex) (equivalent to 0 to 64 decimal)
Starting word address
0000 to 07FF (Hex) (equivalent to 0000 to 2047 decimal)
Function
Section 4-6