Test Run In Monitor Mode - Omron CPM2C-S100C Operation Manual

Sysmac cpm2c-s series
Table of Contents

Advertisement

Programming Example
8-3-5

Test Run in MONITOR Mode

1,2,3...
If errors are displayed, edit the program to correct the errors and check the
program again. Continue checking the program until all errors have been cor-
rected.
Switch the CPM2C-S in MONITOR mode and check the operation of the pro-
gram.
1. Set the Programming Console's mode switch to MONITOR mode.
MONITOR
RUN
PROGRAM
2. Press the CLR Key to bring up the initial display.
3. Force-set the start input bit (IR 00000) from the Programming Console to
start the program.
MONTR
The cursor in the lower left corner of the display indicates that the force set
is in progress. The bit will remain ON as long as the Set Key is held down.
4. The output indicator for output IR 01000 will flash ten times if the program
is operating correctly. The indicator should go OFF after ten one-second
flashes.
There is a mistake in the program if the output indicator doesn't flash. In
this case, check the program and force set/reset bits to check operation.
<MONITOR>

CLR

LD
LD

^ OFF

ON
SET
Section 8-3
BZ
00000
199

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpm2c-s110cCpm2c-s100c-drtCpm2c-s110c-drt

Table of Contents