Functions - Omron CPM2C-S100C Operation Manual

Sysmac cpm2c-s series
Table of Contents

Advertisement

Allocation of Word and Bit Addresses
Data area
1
DM
Read/write
area
Error log
3,4
Read-only
3,4
PC Setup
Note
4-1-1

Functions

IR Area
Note
Words
DM 0000 to DM 1999
---
DM 2022 to DM 2047
(2,026 words)
DM 2000 to DM 2021
---
(22 words)
DM 6144 to DM 6599
---
(456 words)
DM 6600 to DM 6655
---
(56 words)
1. The contents of the HR area, AR area, Counter area, and read/write DM
area are backed up by the CPU Unit's battery. If the battery is removed or
fails, the contents of these areas will be lost and returned to default values.
2. When a TC numbers is used as a word operand, the timer or counter PV
is accessed; when used as a bit operand, its Completion Flag is accessed.
3. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but
they can be changed from a Programming Device.
4. The program and data in DM 6144 to DM 6655 are stored in flash memory.
The functions of the IR area are explained below.
IR area bits from IR 00000 to IR 01915 are allocated to terminals on the CPU
Unit and Expansion I/O Units. IR words that are not allocated to inputs or out-
puts can be used as work words. Input words begin with IR 000 and output
words begin with IR 010.
1. The input bits shown in the following tables can operate as normal inputs
or they can be assigned special functions in the PC Setup.
Special functions for input bits IR 00000 through IR 00002 are set in
DM 6642:
Bit
address
IR 00000
Used as normal
inputs.
IR 00001
IR 00002
Special functions for input bits IR 00003 and IR 00004 are set in DM 6628:
Bit
address
DM 6628
IR 00003
00 to 03
IR 00004
04 to 07
Bits
DM area data can be accessed in word units
only. Word values are retained when the
power is turned off, or operation started or
stopped.
Read/write areas can be read and written
freely within the program.
Used to store the time of occurrence and
error code of errors that occur. These words
can be used as ordinary read/write DM when
the error log function isn't being used.
Cannot be overwritten from program.
Used to store various parameters that con-
trol PC operation.
PC Setup setting (DM 6642 bits 08 to15)
00
01
Used as high-speed
counter inputs.
Bits in
PC Setup setting (in DM 6628)
0
Used as normal
inputs.
Section 4-1
Function
02, 03, or 04
Used as inputs for
synchronized pulse control.
Used as a normal input.
1
Used as
Used as
interrupt inputs
quick-response
(including
inputs.
counter mode).
2
85

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpm2c-s110cCpm2c-s100c-drtCpm2c-s110c-drt

Table of Contents