7.5 DNP COMMUNICATIONS
The following table specifies the default variation for all objects returned by the relay. These are the variations that will be
returned for the object in a response when no specific variation is specified in a request.
DEFAULT VARIATIONS
OBJECT
DESCRIPTION
1
Binary Input - Single Bit
2
Binary Input Change With Time
10
Binary Output Status
30
16-Bit Analog Input Without Flag
32
16-Bit Analog Input Change Without Time
a) BINARY INPUT / BINARY INPUT CHANGE
BINARY INPUT (OBJECT 01);
BINARY INPUT CHANGE (OBJECT 02)
INDEX
DESCRIPTION
0
Relay In Service
1
Trip Condition(s) Active
2
Alarm Condition(s) Active
3
Protection Picked Up
4
Setpoint Group 1 Active
5
Setpoint Group 2 Active
6
Setpoint Group 3 Active
7
Setpoint Group 4 Active
8
Breaker Is Open
9
Breaker Is Closed
10
Reclosure Enabled
11
Reclosure Disabled
12
Reclosure In Progress
7
13
Reclosure Locked Out
14
Local Mode Active
15
Diagnostic Message(s) Active
16
Major Internal Failure
17
Minor Internal Failure
18
Testing Mode Active
19
Contact Input 1 Closed
20
Contact Input 2 Closed
21
Contact Input 3 Closed
Notes:
1.
Any detected change in the state of any point will cause the generation of an event object.
2.
An event object will be generated as a result of any change in any point.
7-52
Courtesy of NationalSwitchgear.com
EVENT
CLASS
ASSIGNED
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
1
Class 1
1
Class 1
1
Class 1
1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
750/760 Feeder Management Relay
DEFAULT
VARIATION
1
2
2
4
2
BINARY INPUT (OBJECT 01);
BINARY INPUT CHANGE (OBJECT 02)
INDEX
DESCRIPTION
22
Contact Input 4 Closed
23
Contact Input 5 Closed
24
Contact Input 6 Closed
25
Contact Input 7 Closed
26
Contact Input 8 Closed
27
Contact Input 9 Closed
28
Contact Input 10 Closed
29
Contact Input 11 Closed
30
Contact Input 12 Closed
31
Contact Input 13 Closed
32
Contact Input 14 Closed
33
Setpoint Access Jumper Present
34
Coil Monitor 1 Circuit Closed
35
Coil Monitor 2 Circuit Closed
36
Relay 1 TRIP Operated
37
Relay 2 CLOSE Operated
38
Relay 3 AUXILIARY Operated
39
Relay 4 AUXILIARY Operated
40
Relay 5 AUXILIARY Operated
41
Relay 6 AUXILIARY Operated
42
Relay 7 AUXILIARY Operated
43
Relay 8 SERVICE Operated
7 COMMUNICATIONS

7.5.3 DNP POINT LISTS

EVENT
CLASS
ASSIGNED
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
GE Multilin