Section 15
Control
15.1.3.2
686

Single circuit breaker with double busbar, external voltage selection

Bus 1
Fuse
VT
bus Voltage
VREF1
Voltag
Line
e
V
VA/VB/
C
ANSI10000094 V1 EN-US
Figure 309:
Connection of SESRSYN (25) function block in a single breaker,
double busbar arrangement with external voltage selection
In this type of arrangement no internal voltage selection is required. The voltage
selection is made by external relays typically connected according to figure 309.
Suitable voltage and VT fuse failure supervision from the two busbars are selected
based on the position of the busbar disconnectors. This means that the connections to
the function block will be the same as for the single busbar arrangement. The voltage
selection parameter CBConfig is set to No voltage sel.
Bus 2
Fuse
VT
189
289
152
1/2/3
Fuse
VT
Line
1MRK 504 163-UUS A
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000094-1-en.vsd
Transformer protection RET670 2.2 ANSI
Application manual
M12325-3 v8