80 Electrical installation

Connecting the power cables

Connection diagram

ACS580-01
L1
PE
2b
2a
(PE)
PE
(PE)
L1
1
For alternatives, see section
2
Use a separate grounding PE cable (2a) or a cable with a separate PE conductor (2b)
if the conductivity of the shield does not meet the requirements for the PE conductor
(see page 58).
3
360-degree grounding is recommended if shielded cable is used. Ground the other end
of the input cable shield or PE conductor at the distribution board.
4
360-degree grounding is required.
5
External brake resistor
6
Use a separate grounding cable if the shield does not meet the requirements of
IEC 61439-1 (see page 58) and there is no symmetrically constructed grounding
conductor in the cable (see page 61).
Note:
If there is a symmetrically constructed grounding conductor on the motor cable in addition to
the conductive shield, connect the grounding conductor to the grounding terminal at the drive
and motor ends.
Do not use an asymmetrically constructed motor cable for motors above 30 kW (see page 58).
Connecting its fourth conductor at the motor end increases bearing currents and causes extra
wear.
L2
L3
3
1
L2
L3
Selecting the supply disconnecting device
UDC+
R-
R+
3
5
T1/U T2/V T3/W
4
V1
W1
U1
3 ~ M
on page
57.
6