Connecting The Power Cables; Connection Diagram - ABB ACS880-07 Hardware Manual

45 to 710 kw, 50 to 700 hp
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Connecting the power cables

Connection diagram

ACS880-07
*)
PE
1a
1b
(PE)
PE
(PE)
1
Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b) if the
conductivity of the shield does not meet the requirements for the PE conductor (see page 84).
2
360-degree grounding is recommended if shielded cable is used. Ground the other end of the input
cable shield or PE conductor at the distribution board.
3
360-degree grounding is required.
4
Line contactor (option +F250)
5
Common mode filter (option +E208)
6
du/dt filter or sine filter (options +E205 and +E206)
7
Use a separate grounding cable if the shield does not meet the requirements of IEC 61439-1 (see
page 84) and there is no symmetrically constructed grounding conductor in the cable (see page 86).
8
External brake resistor
9
Terminals of frame R9 cabinet:
UDC+
R-
R+ UDC-
10
Drive module
10
4
R-
UDC- UDC+
9
L1
L2
L3
R-
2
L1
L2
L3
Electrical installation 107
L1/
L3/
L2/
~
U1
W1
V1
~
UDC+
T1/
T2/
T3/
R+ UDC-
U2
V2
W2
R+
U2
V2
W2
2
3
V1
W1
U1
8
3 ~ M
5
6
7