220 Optional I/O extension modules
External power supply
The external power supply is needed only if you want to connect an external back-up
power supply for the drive control board.
Note: Frames R0...R4 need CMOD-02 for connecting external power supply, frames
R5...R9 have corresponding terminals 40 and 41 on the control board.
Marking
40
24V AC/DC + in External 24 V (AC/DC) input
41
24V AC/DC - in
General cabling instructions
Obey the instructions given in chapter
Wiring
Connect the external control cables to the applicable module terminals. Ground the
outer shield of the cables 360 degrees under a grounding clamp on the grounding
shelf of the control cables
Motor thermistor connection example
1)
1)
One or 3...6 PTC thermistors connected in series.
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and
wiring are reinforced/double insulated, voltages on the PTC wiring are within SELV
limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and
CMOD-02 PTC terminal.
Description
External 24 V (AC/DC) input
Planning the electrical installation
PTC IN
60
PTC IN
61
CMOD-02
on page 57.