Cooling data and noise

The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O, options and panel not in use) and
maximum load (all digital inputs and relays in the ON state, and the panel, fieldbus
and fan in use). The total heat dissipation is the sum of the heat dissipation in the
main and control circuits. Use the maximum heat dissipation when designing cabinet
or electrical room cooling needs.
Type
ACS580
Main circuit
-01-
at rated
I
at I
1N
W
3-phase U
= 400 or 480 V (380...415 V, 440...480 V)
N
02A6-4
20
03A3-4
30
04A0-4
41
05A6-4
59
07A2-4
81
09A4-4
108
12A6-4
149
017A-4
203
025A-4
297
032A-4
405
038A-4
500
045A-4
594
062A-4
810
073A-4
999
061A-4
1117
072A-4
1117
087A-4
1120
105A-4
1295
145A-4
1440
169A-4
1940
206A-4
2310
246A-4
3300
293A-4
3900
363A-4
4800
430A-4
6000
Heat dissipation
Control
Control
circuit
circuit
minimum
maximum
N
W
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
3.5
25
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
4.1
36
Main and
control boards
maximum
W
W
45
55
66
84
106
133
174
228
322
430
525
619
835
1024
1153
1153
1156
1331
1476
1976
2346
3336
3936
4836
6036
Air flow
Noise Frame
3
m
/h
dB(A)
34
56
34
56
34
56
34
56
50
55
50
55
50
55
128
66
128
66
116
71
116
71
116
71
134
69
134
69
280
62
280
62
280
62
435
67
435
67
450
67
550
67
550
65
1150
65
1150
68
1150
68
3AXD00000586715.xls G
size
R0
R0
R0
R0
R1
R1
R1
R2
R2
R3
R3
R3
R4
R4
R5
R5
R5
R6
R6
R7
R7
R8
R8
R9
R9