Relay output connection example
RO PTC C
62
63
RO
PTC B
X4
OUT1
34
OUT2
35
SGND
36
IN1
37
IN2
38
Power supply connection example
1)
1)
External power supply, 24 V AC/DC
WARNING!
control board is powered using an external 24 V AC supply.

Start-up

Setting the parameters
1. Power up the drive.
2. If no warning is shown,
make sure that the value of both parameter 15.02 Detected extension module
and parameter 15.01Extension module type is CMOD-02.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 Detected extension module is
CMOD-02.
set parameter 15.01 Extension module type to CMOD-02.
CMOD-02
CCU
+
40
-
41
Do not connect the +24 V AC cable to the control board ground when the
Optional I/O extension modules 221
24V AC/DC + in
24V AC/DC - in
CMOD-02