Efficiency; Degree Of Protection; Ambient Conditions - ABB ACS580-01 Hardware Manual

Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

Auxiliary circuit power consumption

Efficiency

Degree of protection

Ambient conditions

Environmental limits for the drive are given below. The drive is to be used in a heated, indoor,
controlled environment. All printed circuit boards are conformal coated.
Installation site altitude
Air temperature
Relative humidity
Maximum external power supply:
Frames R0...R4: 25 W, 1.04 A at 24 V AC/DC (with
option modules CMOD-01, CMOD-02)
Frames R5...R9: 36 W, 1.50 A at 24 V AC/DC (as
standard, terminals 40...41)
Approximately 98% at nominal power level
IP21 (UL type 1)
IP55 (UL type 12)
Operation
installed for
stationary use
• 0 to 4000 m
-
(13123 ft)
above sea level
1)
• 0 to 2000 m
(6561 ft) above
2)
sea level
Output derated
above 1000 m
(3281 ft), see
page 140.
-15 to +50 °C (5 to
-40 to +70 °C (-40
122 °F).
to +158 °F)
0 to -15 °C (32 to
5 °F): No frost
allowed.
See section
Ratings.
5 to 95%
Max. 95%
No condensation allowed. Maximum allowed relative
humidity is 60% in the presence of corrosive gases.
Technical data 159
Storage
Transportation
in the protective
in the protective
package
-
-40 to +70 °C (-40
to +158 °F)
Max. 95%
package

Advertisement

Table of Contents
loading

Table of Contents