150 Technical data
Maximum recommended motor
cable length
Operational functionality and motor cable length
The drive is designed to operate with optimum performance
with the following maximum motor cable lengths.
Note: Conducted and radiated emissions of these motor
cable lengths do not comply with EMC requirements.
Frame
Maximum motor cable length, 4 kHz
size
Scalar control
m
Standard drive, without external options
R0
100
R1
100
R2
200
R3
300
R4
300
R5
300
R6
300
R7
300
R8
300
R9
300
Note: In multimotor systems, the calculated sum of all
motor cable lengths must not exceed the maximum motor
cable length given in the table.
EMC compatibility and motor cable length
To comply with the European EMC Directive (standard
EN 61800-3), use the following maximum motor cable
lengths at 4 kHz switching frequency. See the table below.
Vector control
ft
m
330
100
330
100
660
200
990
300
990
300
990
300
990
300
990
300
990
300
990
300
3AXD00000586715.xls G
ft
330
330
660
990
990
990
990
990
990
990