ABB ACS580-01 Hardware Manual page 103

Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

Connection examples of two-wire and three-wire sensors
Hand/Auto, Hand/PID, and PID macros (see ACS580 firmware manual
(3AXD50000016097 [English])) use analog input 2 (AI2). The macro wiring diagrams
on these pages use an externally powered sensor (connections not shown). The
figures below give examples of connections using a two-wire or three-wire
sensor/transmitter supplied by the drive auxiliary voltage output.
Note: Maximum capability of the auxiliary 24 V DC (250 mA) output must not be
exceeded.
Two-wire sensor/transmitter
-
4...20 mA
P
+
I
Note: The sensor is supplied through its current output and the drive feeds the supply
voltage (+24 V DC). Thus the output signal must be 4...20 mA, not 0...20 mA.
Three-wire sensor/transmitter
OUT
(0)4...20 mA
P
-
I
+
X1
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
AGND
...
10 +24V
Auxiliary voltage output, non-isolated,
+24 V DC, max. 250 mA
11 DGND
X1
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
AGND
...
10 +24V
Auxiliary voltage output, non-isolated,
+24 V DC, max. 250 mA
11 DGND
Electrical installation 103
= 100 ohm
in
= 100 ohm
in

Advertisement

Table of Contents
loading