Notes:
1)
Current [0(4)...20 mA, R
with switch S1 (AI1). Change of setting requires changing the corresponding parameter.
2)
Current [0(4)...20 mA, R
with switch S2 (AI2). Change of setting requires changing the corresponding parameter.
3)
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on the board.
4)
AI1 is used as a speed reference if vector control is selected.
5)
In scalar control (default): See Menu - Primary settings - Start, stop, reference - Constant
frequencies or parameter group 28 Frequency reference chain.
In vector control: See Menu - Primary setting - Start, stop, reference - Constant speeds or
parameter group 22 Speed reference selection.
DI3 DI4
Scalar control (default)
0
0
Set frequency through AI1
1
0
28.26 Constant frequency 1
0
1
28.27 Constant frequency 2
1
1
28.28 Constant frequency 3
6)
In scalar control (default): See Menu - Primary settings - Ramps or parameter group 28
Frequency reference chain.
In vector control: See Menu - Primary settings - Ramps or parameter group 23 Speed
reference ramp.
DI5 Ramp
set
Scalar control (default)
0
1
28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
1
2
28.74 Freq acceleration time 2
28.75 Freq deceleration time 2
7)
Connected with jumpers at the factory.
8)
Note: Use shielded twisted-pair cables for digital signals.
9)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
Further information on the usage of the connectors and switches is given in the sections below.
See also section
Control connection data
= 100 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage [ 0(2)...10 V, R
in
Operation/Parameter
on page 152.
Electrical installation 99
> 200 kohm] input selected
in
> 200 kohm] input selected
in
Vector control
Set speed through AI1
22.26 Constant speed 1
22.27 Constant speed 2
22.28 Constant speed 3
Parameters
Vector control
23.12 Acceleration time 1
23.13 Deceleration time 1
23.14 Acceleration time 2
23.15 Deceleration time 2