ABB ACS580-01 Hardware Manual page 212

Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

212 Optional I/O extension modules
Transistor output
Marking
42
DO1 SRC
43
DO1 OUT
44
DO1 SGND
External power supply
The external power supply is needed only if you want to connect an external back-up
power supply for the drive control board.
Note: Frames R0...R4 need CMOD-01 for connecting external power supply, frames
R5...R9 have corresponding terminals 40 and 41 on the control board.
Marking
40
24V AC/DC + in
41
24V AC/DC - in
General cabling instructions
Obey the instructions given in chapter
Wiring
Connect the external control cables to the applicable module terminals. Ground the
outer shield of the cables 360 degrees under a grounding clamp on the grounding
shelf of the control cables.
Relay output connection example
24 V DC
Digital output connection example
24 V DC
Description
Source input
Digital or frequency output
Ground (earth) potential
Description
External 24 V (AC/DC) input
External 24 V (AC/DC) input
Planning the electrical installation
RO4C
50
RO4A
51
RO4B
52
CMOD-01
42
DO1 SRC
43
DO1 OUT
DO1 SGND
44
CMOD-01
on page 57.