Power cable connection

For alternatives, see
Planning the electrical
installation:
Disconnecting device
(means).

Connecting the power cables

• Connect the twisted shield of the cable to the drive grounding terminal. Note:
cable lugs are needed in frame sizes R2 and R3.
• Supply cable grounding: If shielded cable is used, and the conductivity of the
shield is < 50% of the conductivity of the phase conductor, use a separate PE
cable (1) or a cable with a grounding conductor (2). With shielded cable 360°
grounding of the supply cables is recommended.
Motor cable grounding: Use a separate grounding cable (3) if the conductivity of
the cable shield is < 50% of the conductivity of the phase conductor and there is
no symmetrically constructed grounding conductor in the cable (see Planning the
electrical installation:
360 degrees grounding is required at the cabinet entry in first environment
installations. First environment EMC compliance is defined in chapter
data.
Note: If there is a symmetrically constructed grounding conductor in the motor
cable in addition to the conductive shield, connect the grounding conductor to the
grounding terminal at the drive and motor ends.
Note: Do not use an asymmetrically constructed motor cable. Connecting its
fourth conductor at the motor end increases bearing currents and causes extra
wear.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Power cable connection
INPUT
PE
U1
V1 W1
1)
2)
(PE)
PE
(PE)
L1
L2
L3
Selecting the power
Drive with brake chopper included
UDC+
UDC
-
R
R+
External brake
resistor (360
degrees grounding
required)
cables).
-
OUTPUT
U2 V2 W2
3)
V1
W1
U1
~
3
Motor
Technical
Electrical installation
61