ABB ACS580-01 Hardware Manual page 30

Hide thumbs Also See for ACS580-01:
Table of Contents

Advertisement

30 Operation principle and hardware description
Frames R6...R9
The layout of a frame R6 drive is presented below. The constructions of frames
R7...R9 differ to some extent.
R6...R9
5
1
5
4
5
1
1
Mounting points (2 at the top, 2 at the
bottom of the main part of the frame, 2 at
the top of the cable box)
2
Cover
3
Cable box
4
Heatsink
5
Lifting holes (6 pieces)
6
Assistant control panel
7
Control panel connection
8
Cold configuration connection for CCA-01
9
Power OK and Fault LEDs. See section
LEDs
on page 130.
10 I/O connections. See section
control connection terminals, frame
R5...R9
on page 33.
11 Cable tie mounts for I/O cables
12 Clamps for I/O cable mechanical support
2
3
External
20
6
14
PE
16
19
18
13 Varistor grounding screw (VAR), under
the control panel platform
14 Two EMC filter grounding screws (EMC),
one under the control panel platform and
one at the left, above the shroud.
See
Checking the compatibility with IT
(ungrounded) and corner-grounded TN
systems
on page 75.
15 Shroud. Under the shroud: Input power
connection (L1, L2, L3), motor connection
(T1/U, T2/V, T3/W) and DC connection
(UDC+, UDC-).
16 PE connection (power line)
17 Grounding connection (motor)
18 Lead-through plate
19 Main cooling fan
20 Auxiliary cooling fan
14
13
7
8
9
9
11
10
12
12
15
17

Advertisement

Table of Contents
loading

Table of Contents