102 Electrical installation
Connection for obtaining 0...10 V from analog output 2 (AO2)
To obtain 0...10 V from analog output AO2, connect a 500 ohm resistor (or two
1 kohm resistors in parallel) between the analog output 2 AO2 and analog common
ground AGND.
Examples are shown in the figure below.
500 ohm
1 kohm
X1
8 AO2
9 AGND
X1
8 AO2
1 kohm
9 AGND
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected
to chassis through a 2 Mohm resistor.
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected
to chassis through a 2 Mohm resistor.