Digital inputs DI1...DI6
(Term. 13...18)
Relay outputs RO1...RO3
(Term. 19...27)
Analog inputs AI1 and AI2
(Term. 2 and 5)
Analog outputs AO1 and AO2
(Term. 7 and 8)
Reference voltage output for
analog inputs +10V DC
(Term. 4)
Safe torque off (STO) inputs IN1
and IN2
(Term. 37 and 38)
Input type: NPN/PNP
Terminal size:
Frames R0...R4: 0.14...1.5 mm
Frames R5...R9: 0.14...2.5 mm
DI1...DI5 (Term.13...17)
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
R
: 3 kohm
in
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
DI6 (Term.18)
Can be used as a digital or frequency input.
12/24 V DC logic levels: "0" < 3 V, "1" > 8 V
R
: 3 kohm
in
Max. frequency 16 kHz
Symmetrical signal (duty cycle D = 0.50)
250 V AC / 30 V DC, 2 A
Terminal size:
Frames R0...R4: 0.14...1.5 mm
Frames R5...R9: 0.14...2.5 mm
See sections
Isolation areas, R0...R4 (CCU-11):
155
and
Isolation areas, R5...R9 (CCU-12):
Current/voltage input mode selected with a dip switch, see
page 100.
Current input: 0(4)...20 mA, R
Voltage input: 0(2)...10 V, R
Terminal size:
Frames R0...R4: 0.14...1.5 mm
Frames R5...R9: 0.14...2.5 mm
Inaccuracy: typical ±1%, max. ±1.5% of full scale
Current/voltage output mode for AO1 selected with a dip
switch, see page 100.
Current output: 0...20 mA, R
Voltage output: 0...10 V, R
Terminal size:
Frames R0...R4: 0.14...1.5 mm
Frames R5...R9: 0.14...2.5 mm
Inaccuracy: ±1% of full scale (in voltage and current
modes)
Max. 20 mA output
Inaccuracy: ±1%
24 V DC logic levels: "0" < 5 V, "1" > 13 V
R
: 2.47 kohm
in
Terminal size:
Frames R0...R4: 0.14...1.5 mm
Frames R5...R9: 0.14...2.5 mm
Technical data 153
2
2
2
2
on page 156.
: 100 ohm
in
: > 200 koh
in
2
2
: < 500 ohm
load
: > 100 kohm (AO1 only)
load
2
2
2
2
on page