Frequency output connection example
1)
1)
An externally supplied frequency indicator which provides, for example:
• a 40 mA / 12 V DC power supply for the sensor circuit (CMOD frequency output)
• suitable voltage pulse input (10 Hz ... 16 kHz).
External power supply connection example
1)
1)
External power supply, 24 V AC/DC
WARNING!
control board is powered using an external 24 V AC supply.

Start-up

Setting the parameters
1. Power up the drive.
2. If no warning is shown,
make sure that the value of both parameter 15.02 Detected extension module
and parameter 15.01Extension module type is CMOD-01.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 Detected extension module is
CMOD-01.
set parameter 15.01 Extension module type to CMOD-01.
You can now see the parameters of the extension module in parameter group 15
I/O extension module.
3. Set the parameters of the extension module to applicable values.
42
43
44
+
40
-
41
Do not connect the +24 V AC cable to the control board ground when the
Optional I/O extension modules 213
DO1 SRC
DO1 OUT
DO1 SGND
CMOD-01
24V AC/DC + in
24V AC/DC - in
CMOD-01