94 Electrical installation
Note 2 for frames R8...R9: The connectors are detachable but we do not
recommend that you detach them. If you do, detach and reinstall the connectors
as follows.
Terminals L1, L2 and L3
•
Remove the combi screw that attaches the connector to its terminal post, and
pull the connector off.
•
Put the conductor under the connector pressure plate and pre-tighten the
conductor.
•
Put the connector back onto the terminal post. Start the combi screw, and turn
it at least two rotations by hand.
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
•
Tighten the combi screw to a torque of 30 N·m (22 lbf·ft).
•
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m
(52 lbf·ft) for frame R9.
Terminals T1/U, T2/V and T3/W
•
Remove the nut that attaches the connector to its busbar.
•
Put the conductor under the connector pressure plate and pre-tighten the
conductor.
•
Put the connector back to its busbar. Start the nut, and turn it at least two
rotations by hand.
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
•
Tighten the nut to a torque of 30 N·m (22 lbf·ft).
•
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m
(52 lbf·ft) for frame R9.