Relay cable
The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL,
Germany) has been tested and approved by the manufacturer.
Control panel cable
In remote use, the cable connecting the control panel to the drive must not exceed
100 m (330 ft). If multiple drives are connected, the total length of the panel bus must
not exceed 100 m (330 ft).
The cable type tested and approved by the manufacturer is used in control panel
option kits. Suitable cables are CAT 5e unshielded or shielded twisted pair cables.
Drive composer PC tool cable
Connect the Drive composer PC tool to the drive through the USB port of the control
panel. Use a USB type A (PC) - type B (control panel) cable. The maximum length of
the cable is 3 m (9.8 ft).
FPBA-01 PROFIBUS DP adapter module connectors
Frames R0...R3: The following connector types have been tested to fit in the tight
space for option slot 1.
• Phoenix Contact SUBCON-PLUS-PROFIB/PG/SC2, part number 2708245. Lead
the cable through the control cable hole on the right in the lead-through plate (1).
• Siemens, part number 6GK1 500 0EA02. Lead the cable through the middle
control cable hole in the lead-through plate (2).
1
2
Planning the electrical installation 63