88 Electrical installation

Connection procedure, frame R5

Prepare the drive and the cables
WARNING! If the drive will be connected on an IT (ungrounded) system, make
sure you have disconnected the EMC filter and ground-to-phase varistor. See
page 75. If the drive will be connected on a corner-grounded TN system, make sure
you have disconnected the EMC filter. See page 75.
1. Attach the residual voltage warning sticker in the local language next to the
control board.
2. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver (2a). Knock out holes in the
shroud for the cables to be installed (2b).