Endress+Hauser Proline Prosonic Flow B 200 Operating Instructions Manual page 93

Ultrasonic transit time flowmeter
Hide thumbs Also See for Proline Prosonic Flow B 200:
Table of Contents

Advertisement

Proline Prosonic Flow B 200 HART
Parameter
Assign simulation process variable
Process variable value
Simulation current input 1
Value current input 1
Simulation current output 1 to 2
Value current output 1 to 2
Frequency Output Simulation
Frequency Value
Pulse output simulation
Pulse value
Endress+Hauser
Parameter overview with brief description
Prerequsite
One of the following options is
selected in the Assign
simulation process variable
parameter (→  93):
• Volume flow
• Corrected volume flow
*
• Methane fraction
• Corrected methane volume
*
flow
• Mass flow
*
• Temperature
*
• Energy flow
*
• Wobbe index
*
• Calorific value
• Flow velocity
• Sound velocity
In the Simulation current
input parameter the On option
is selected.
In the Simulation current
output 1 to 2 parameter, the
On option is selected.
The Frequency option is
selected in the Operating
mode parameter.
The On option is selected in
the Frequency Output
Simulation parameter.
The Pulse option is selected in
the Operating mode
parameter.
In the Pulse output
simulation parameter
(→  93), the Down-
counting value option is
selected.
Description
Select a process variable for
the simulation process that is
activated.
Enter the simulation value for
the selected process variable.
Switch simulation of the
current input on and off.
Enter the current value for
simulation.
Switch the simulation of the
current output on and off.
Enter the current value for
simulation.
Switch the simulation of the
frequency output on and off.
Enter the frequency value for
the simulation.
Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
(→  70) defines the
pulse width of the pulses
output.
Enter the number of pulses for
simulation.
Commissioning
Selection / User
Factory setting
entry
• Off
Off
• Volume flow
• Corrected volume
flow
• Methane fraction
• Corrected methane
volume flow
• Mass flow
• Temperature
• Energy flow
• Wobbe index
• Calorific value
• Flow velocity
• Sound velocity
Depends on the
0
process variable
selected
• Off
Off
• On
3.59 to 22.5 mA
3.59 mA
• Off
Off
• On
3.59 to 22.5 mA
3.59 mA
• Off
Off
• On
0.0 to 1 250.0 Hz
0.0 Hz
• Off
Off
• Fixed value
• Down-counting
value
0 to 65 535
0
93