Endress+Hauser Proline Prosonic Flow B 200 Operating Instructions Manual page 132

Ultrasonic transit time flowmeter
Hide thumbs Also See for Proline Prosonic Flow B 200:
Table of Contents

Advertisement

Technical data
Output signal
132
Current input
The measured values are written from the automation system to the measuring device via
the current input →  131.
HART protocol
The measured values are written from the automation system to the measuring device via
the HART protocol. The pressure transmitter must support the following protocol-specific
functions:
• HART protocol
• Burst mode
16.4
Output
Current output
Current output 1
Current output 2
Resolution
Damping
Assignable measured
variables
Pulse/frequency/switch output
Function
Version
Maximum input values
Voltage drop
Residual current
Pulse output
Pulse width
Maximum pulse rate
Pulse value
Assignable measured
variables
Frequency output
Output frequency
Damping
Pulse/pause ratio
4-20 mA HART (passive)
4-20 mA (passive)
< 1 µA
Adjustable: 0.0 to 999.9 s
• Volume flow
• Corrected volume flow
• Corrected methane volume flow
• Mass flow
• Energy flow
• Methane fraction
• Calorific value
• Wobbe index
• Temperature
Can be set to pulse, frequency or switch output
Passive, open collector
• DC 35 V
• 50 mA
• For ≤ 2 mA: 2 V
• For 10 mA: 8 V
≤ 0.05 mA
Adjustable: 5 to 2 000 ms
100 Impulse/s
Adjustable
• Volume flow
• Corrected volume flow
• Corrected methane volume flow
• Mass flow
• Energy flow
Adjustable: 0 to 1 000 Hz
Adjustable: 0 to 999 s
1:1
Proline Prosonic Flow B 200 HART
Endress+Hauser