Endress+Hauser Proline Prosonic Flow B 200 Operating Instructions Manual page 81

Ultrasonic transit time flowmeter
Hide thumbs Also See for Proline Prosonic Flow B 200:
Table of Contents

Advertisement

Proline Prosonic Flow B 200 HART
Parameter
Display damping
Damping output 1
Damping output 2
Damping output 2
Measuring mode output 1
Measuring mode output 2
Endress+Hauser
Navigation
"Setup" menu → Output conditioning
Structure of the "Output conditioning" wizard
 26
"Output conditioning" wizard in the "Setup" menu
Parameter overview with brief description
Prerequsite
The measuring device has a
second current output.
The measuring device has a
pulse/frequency/switch
output.
Display damping
Damping out. 1
Damping out. 2
Mode output 1
Mode output 2
Forward flow
Forward/Reverse
End of wizard
Description
Set display reaction time to
fluctuations in the measured
value.
Set the reaction time of the
output signal of the current
output to fluctuations in the
measured value.
Set the reaction time of the
output signal of the second
current output to fluctuations
in the measured value.
Set the reaction time of the
output signal of the frequency
output to fluctuations in the
measured value.
Select measuring mode for
output.
Select measuring mode for
output.
Commissioning
Rev. flow comp.
User entry / 
Factory setting
Selection
0.0 to 999.9 s
3.0 s
0 to 999.9 s
1 s
0 to 999 s
1 s
0 to 999 s
1 s
• Forward flow
Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
• Forward flow
Forward flow
• Forward/Reverse
flow
• Reverse flow
compensation
A0015993-EN
81