P543i/P545i
The angle Alpha should be set equal to the angle of the total impedance Z
a = Ð Z
T
Resistive reverse (R')
Figure 156: Reactive reach settings
3.6.3
PSB TIMER SETTING GUIDELINES
The Setting PSB Time setting can be calculated as follows:
(
)
f
θ
θ
−
⋅
1
2
∆t
=
f
PS
where
angles q
and q
●
are defined in the following figure
1
2
f
is the nominal frequency
●
nom
●
f
is the maximum Power Swing frequency to be taken into account
PS
Since any power swing with f
swings with f
< 0.5Hz Hz need to be considered for Slow Power Swing detection. We recommended setting f
PS
1Hz because this value provides sufficient security margin.
P54x1i-TM-EN-1
+jX
Z
R
Z
L
Z
T
Z
S
nom
>= 0.5Hz can be detected by the setting-free delta current algorithm, only power
PS
Chapter 10 - Power Swing Functions
:
T
Zone 8
Zone 7
α = ÐZ
T
Resistive forward (+R)
V02751
to
PS
281